Champion Fiberglass Logo  

 

Champion Duct, Fiberglass Conduit
The Superior Alternative to PVC Coated Steel Conduit

        Electrical Conduit Comparisons > Fiberglass Conduit
(RTRC)
PVC
Sch 40
PVC
Sch 80
Galvanized Rigid Steel PVC Coated Conduit Aluminum
Cable Fault
Not Affected Melt / Fuse Melt / Fuse Weld Weld Weld
Corrosion Resistance Fiberglass
Wide Range Limited Limited Poor Limited Limited
Relative Cost, 4" Conduit
1 0.75 1 4 6 3.5
Toxicity/Halogens
No Yes Yes No Yes No
Weight Comparison for 4" Conduit
(lbs. per 100 ft., approx.)
78 234 310 982 982 340
Support Spacing for 4" Conduit (ft)
12 7 7 20 20 15
Temperature Range (°F)
-60° to +250° +40° to +150° +40° to +150° N/A N/A N/A
Handling in Low Temperatures
Excellent Brittle Brittle Excellent Excellent Excellent
Burn Through (Cable Pull)
No Yes Yes No No No
Coefficient of Friction
Using PVC Jacketed Cable

0.38 0.90 0.90 0.55 0.90 0.25
Conductivity
No No No Yes Yes Yes
UV Stable (Sunlight Resistance)
(per UL 1684 & CSA-C22.2 No. 211.3-96)
Good Poor Poor Excellent Poor Excellent
Coefficient of Thermal Expansion
(10 -5 inch/inch/°F) *The coefficient is .7 for the steel and 3.5 for the PVC layer.
1.0 3.5 3.5 0.7 3.5/0.7* 3.5
Distance Between Expansion Joints (in ft) 200 50 50 200 200 50
Impact from Earthquake
Excellent Poor Poor Poor Poor Excellent
Resistance to Rodents & Fire Ants
Excellent Poor Poor Excellent Excellent Excellent
Field Handling
Excellent Good Good Very
Poor
Very Poor Poor
Memory
Yes No No No No No

For more details, download our Product Comparison Chart here. . . Download - PDF